|
Issues Impacting Bridge Painting: an Overview
Chapter 6. Task E - Accelerated Testing
Table of Contents
BACKGROUND
Corrosion detrimentally effects bridges, reducing section
thickness and resulting in a weakened bridge structure that
compromises safety. Corrosion control is normally achieved
by applying a coating system to the steel bridge. Unfortunately,
coating systems do not completely protect and have limited
durability. Moisture vapor penetration, water absorption,
stress from thermal gradients across the coating, and ultraviolet
radiation from sunlight can deteriorate the coating and cause
it to fail prematurely. Furthermore, deicing chemicals and
salts from the atmosphere can penetrate the coating and allow
corrosion to occur at the steel substrate underneath the
seemingly intact coating, causing premature blistering and
delamination.
Types of Coating Failure
Coatings on bridges can fail in many ways. In general,
coating failure is defined as the premature deterioration
of the coating system under normal service conditions with
subsequent corrosion of the structure's steel substrate.
Coating failure may occur because of inadequate substrate
preparation, poor adhesion of the coating, improper coating
application, formulation problems with the coating, or unsuitable
coating selection for a given environment. Additional factors,
such as non-flat bridge geometries with hard-to-coat areas
and exterior forces such as abrasion of the surface and bridge
movement from vehicle traffic also increase the chance of
premature coating failure. TABLE
11 lists the main factors influencing coating failure
as well as the common types of coating failure that occur
on coated steel bridges. Three types of coating failure that
occur frequently are highlighted below:
- Undercutting: Moisture penetration to the steel
substrate and buildup of corrosion products underneath
a coating can cause disbonding and failure of a coating.
Osmosis is an important factor, especially when coatings
are subjected to salt exposure, water immersion, frequent
condensation, or high-humidity environments. A coating
must have strong adhesion to the substrate to be resistant
to undercutting. Organic barrier coatings tend to be less
resistant to undercutting than inorganic zinc and thermally
sprayed metals. The reason is that adhesion of organic
coatings is primarily physical, whereas the adhesion of
inorganic zinc and thermally sprayed metals is a result
of chemical bonds as well. This combined physical and chemical
bond tends to be more durable and more resistant to undercutting.
- Cracking: Cracking, or breaks
in the coating extending from the surface through to the
substrate, are caused by
stresses in the coating film and between the coating and
steel substrate that exceed the strength of the coating.
Cracking results in further water penetration and corrosion
of the steel substrate. Cracking is caused by polymer chain
breakage due to aging and weathering of the paint system
as well as premature failure due to exterior forces such
as bridge movement between overlapping joints.
- Holidays: Holidays are bare or thin areas of the
coated surface where reduced barrier protection can lead
to a concentration of the corrosive environment at the
steel substrate and accelerate corrosion. Holidays and
reduced coating thickness are most often found in areas
that are difficult to coat and are caused by inadequate
coating application. Bridge geometries, such as edges,
corners, welds, overlapping joints, and bolted faying surfaces,
represent areas where uniform coating application is difficult
and non-uniform. Failure of the coating in a critical area,
such as a nut-and-bolt or overlapping joints, can lead
to rapid corrosion, such as pitting and steel loss that
compromises the structural integrity of the bridge. Bridge
geometry and design plays an important role in reducing
coating durability. However, it is often overlooked in
accelerated and long-term field testing procedures because
of the difficulty reproducing similar effects in laboratory
tests.
Coating Properties
A protective coating's function is to prevent
corrosive service environments, (e.g., salt-air atmosphere
or deicing
chemicals) from contacting the underlying steel substrate
and initiating corrosion. To accomplish this function, a
coating must have several properties essential to maintaining
a proper barrier to the environment. Some of the more important
properties are: water permeability resistance, weathering
resistance, sunlight resistance, ease of application, good
adhesion, and abrasion resistance.
As noted, an important property of a coating
is its resistance to water penetration. Two related properties
are coating
dielectric strength and coating resistance to ionic movement.
Water can penetrate a coating either as a liquid or as
a vapor. Water penetration decreases the dielectric strength
of a coating, decreasing its resistivity and making the
coating
less insulative. Water penetration can also cause chemical
breakdown of the coating, allowing increased ionic movement
to the substrate, and further decreasing the useful life
of the coating. Moisture also transports oxygen that is
necessary for corrosion to occur. Since corrosion is an electrochemical
process, ionic and oxygen transport towards the steel substrate
increases the chance of corrosion being initiated. Once
corrosion
has begun, the corrosion products formed can cause undercutting
and loss of adhesion of the coating. Water penetration
may swell the coating and produce stresses that eventually
lift
the coating from the substrate. Although water containing
naturally-occurring salts or deicing chemicals penetrate
coatings at a slightly slower rate than pure water, their
presence increases the likelihood of coating deterioration
and substrate corrosion, since they can accumulate underneath
the coating, cause delamination by blistering, or accelerate
corrosion of the substrate.
Although immersion of a coating in salt water
alone is a severe environment, periods of wetness and dryness
and
frequent changes in temperature can also cause mechanical
damage to a coating. Surprisingly, only small amounts of
atmospheric salts, such as ammonium sulfate or sodium chloride,
need be present to cause coating degradation because wet/dry
cycling tends to enhance ionic movement and concentrate
salt in the coating and at the substrate, leading to accelerated
corrosion rates.
Coating Evaluation
The performance and durability of bridge coatings
are often evaluated by either an accelerated test, such as
a salt-spray
fog, or by long-term atmospheric exposure to a particular
environment. Condition assessment of bridge coatings is accomplished
using ASTM standard methods such as those listed in TABLE 12 to determine the degree of rusting, cracking,
blistering, gloss retention, and adhesion to the substrate.
Most of the ASTM standard methods require visual inspection
of the coating to determine coating degradation and are subjective.
In addition, ASTM B-117, the standard salt-spray test, does
not correlate well with long-term field exposure. For instance,
waterborne coating systems exhibit poor performance using
ASTM B-117, but show improved performance in field environments.
ASTM D-1014, the long-term field exposure test procedure
for coatings, is the best method to judge how well a coating
will last in a particular environment. However, it can take
years to acquire meaningful data. Current accelerated tests
lack credibility as predictors of field service performance.
Electrochemical techniques have also been used
to evaluate bridge coatings. Direct-current electrochemical
measurements
such as linear polarization and potentiodynamic polarization
have been attempted on various coating systems, however,
the complexity of the coating/steel substrate does not
allow accurate interpretation of the data. Electrochemical
impedance
spectroscopy (EIS) measurements, on the other hand, can
resolve these complexities and provide a fast, quantitative
method
of assessing coating properties related to water penetration
and identify the early onset of corrosion of the steel
before it is seen visually. When used in combination with
accelerated
tests and long-term field testing, EIS can be a powerful
technique for comparing a coating's ability to reduce the
corrosion rate of the substrate. In addition, EIS measurements
taken on existing bridge coatings in the field and as part
of a total bridge management program can provide ongoing
data on the condition of the coating. Such information
would allow bridge owners to schedule overcoating before
severe
corrosion of the structure has occurred and ultimately
would reduce overcoating costs and increase the life of the
coating
system.
EIS is capable of probing the electrochemical
interface of a coated metal and providing quantitative information
on the influence of corrosive environments affecting protective
coatings and metallic substrates. For example, an EIS scan
of a well-coated sample gives a high electrical resistance
(Rc), and low capacitance (Cc), due
to the dielectric property of the protective coating. The
steel substrate properties are not measurable and corrosion
is not occurring under the coating because the substrate
has not been exposed to corrosive elements such as salt
and oxygen. If the coating is subjected to an electrolyte
by
immersion, accelerated salt spray, or atmospheric exposure,
the electrolyte can eventually permeate the coating, reducing
Rc and increasing Cc, The change
in these parameters is related to water penetration into
the
coating and indicates that the coating is degrading. Furthermore,
electrolyte and oxygen may penetrate to the steel substrate
and initiate corrosion of the steel substrate. At this
point, the polarization resistance (Rp) and
capacitance (Cp) properties related to the steel
corrosion rate will become measurable. EIS parameters such
as Rp,
Cp, Rc, and Cc, can be
plotted versus time to determine how well they correlate
with the
rate of deterioration and the onset of corrosion for each
coating.
Another important EIS parameter that has been
used to correlate steel corrosion is the frequency at maximum
phase angle (wmax).
The frequency at maximum phase angle is given by the equation:
This equation is independent of area because the area dependence
of Rp and Cp and Rp and
Rs, the electrolyte resistance, cancel out each
other. The area-independence of wmax is
desirable property since the active, corroding steel area
under a coating is usually not known. Research by G.T. Ruck
et al. (9) has shown that for
bare steel pipe in soil, wmax stayed relatively
constant with time when the corrosion rate was low and the
pipe was protected. However, wmax decreased
two orders of magnitude when the pipe was not protected and
the corrosion rate increased. The same decreasing trend of wmax can
be used to determine the onset of corrosion underneath a
coating. Further details on the EIS technique and the important
parameters measured are given in Appendix
A.
OBJECTIVES AND APPROACH
The objectives of this task were: (1) to identify
potential accelerated test methods that improve the evaluation
of bridge
coating performance and (2) to use these methods to evaluate
the corrosion resistance and weathering performance of several
coatings.
Three accelerated test procedures were identified
and used to evaluate the performance and durability of five
bridge
coatings: (1) a cyclic salt-spray exposure test (2) a test
combining cyclic salt-spray exposure, a freeze/thaw cycle,
and carbon-arc, ultraviolet-light exposure, and (3) an
electrolyte immersion test. Four of the five coatings studied
were thermally
sprayed zinc, aluminum, and zinc/aluminum, and a three-part
VOC-compliant coating system. Test panels were also cut
from a bridge section removed from service that contained
a naturally
weathered, red-lead primer/alkyd topcoat. In addition to
flat test panels, non-flat panels were constructed to simulate
a welded section and a bolted faying surface configuration
commonly found on bridges. EIS was performed periodically
on the test panels in the immersion experiments and before,
during, and after the two cyclic tests to quantify coating
resistance and capacitance (Rc and Cc),
polarization resistance and capacitance (Rp and
Cp), and the frequency at maximum phase angle
(wmax). Consumption rates of the metallic
coatings and corrosion rates of the steel substrate were
calculated from Rc and Rp. Visual
and photographic inspection of the test panels were also
performed
before and after testing.
MATERIALS AND PROCEDURES
Test-Panel Preparation
Experimenters prepared 99 coated test panels for exposure
in the three accelerated tests. Of these test specimens,
94 wer 10.0- by 15.0- by 0.64-cm (4- by 6- by 0.25-in), ASTM
A36, hot-rolled, carbon steel plates that were either grit-blasted
with a G-40 grit to a white-metal finish (SP-5), or were
left with as-received millscale. The remaining five test
panels were cut from a coated bridge section that had been
taken out of service. Of the test panels, 52 contained either
of 2 modifications: a welded steel support or 2 right-angle
brackets welded to the panel and attached to each other with
2 nuts and bolts (as shown in FIGURE 63). The non-flat geometries were used in the
two cyclic tests to simulate welded sections and bolted,
faying configurations (surfaces that are difficult to coat
properly). TABLE 13 summarizes
the test specimens used in the experiments. The flat panels
and flat panels with the welded steel supports were purchased
from KTA-Tator Company. Additional KTA-Tator-supplied flat
panels were modified to construct the welded and bolted right-angle
bracket configurations.
Coating Type and Application
Five coatings systems were evaluated in this
task: thermally sprayed (TS) zinc, aluminum, and 85/15 Zn/Al,
a VOC-compliant
coating system; and a weathered, red-lead primer/alkyd topcoat
taken from a bridge section that had been removed from service.
The VOC-compliant coating system consisted of a three-component
zinc-filled, epoxy primer [(VOC, 302 g/L (2.52 lb/gal)];
a two- component, high-build, modified aluminum epoxy mastic
intermediate coat [VOC, 89 g/L (0.74 lb/gal)]; and a high-gloss,
high-solids, aliphatic polyurethane topcoat [VOC, 288 g/L
(2.4 lb/gal)]. The bridge section containing the red-lead
primer/alkyd topcoat was obtained from the Illinois Department
of Transportation (IDOT). Further information on the thermally
sprayed metal coatings are given in the previous task. Application
of the coatings was done following either manufacturing recommendations
or standard practices. Prior to coating, the test panels
were ultrasonically cleaned in trichloromethane to remove
any grease or dirt on the surface. After coating, thickness
measurements were performed using either an Elcometer thickness
gauge or Positector-2000 thickness gauge. Wet thickness was
also measured on the VOC-compliant coating as recommended
by the manufacturer.
Linear polarization, potentiodynamic polarization,
and EIS were made on ASTM A36 carbon-steel rods that were
left
bare or thermally sprayed with zinc, aluminum or Zn/Al.
Initial consumption rates of the metallic coatings and initial
corrosion
rates of the steel substrate were obtained for comparison
with values obtained from the three accelerated exposure
tests. Any change in the metallic coating consumption rate
or steel corrosion rate would mean that the metallic coating
has become ineffective and that significant corrosion of
the steel is occurring.
The carbon-steel rods were grit-blasted to
a white-metal finish (SSPC-10) or left with original millscale.
The electrolyte
used was 0.40 percent ammonium sulfate and 0.05 percent sodium
chloride. Two thermally sprayed coating thicknesses were
coated onto the steel rods [75 µm (0.003 in) and 150 µm
(0.006 in). The 75-µm thickness represents a coating
of minimal through-porosity and the 150-µm thickness
a flow-through porous coating. The experiments were performed
in triplicate and average values of Rp, Cp,
Rc, Cc, and wmax were
obtained. Coating consumption rates and steel corrosion rates
were calculated from Rc and Rp. The
carbon-steel rods were thermally sprayed by ASB Industries,
Incorporated, Barberton, Ohio.
The linear
polarization and potentiodynamic polarization experiments
were carried out using the Model 342C Soft corrTM corrosion
measurement system. The system uses and EG&G Princeton
Applied Research Model 273 potentiostat driven by software
in an IBM computer. The EIS measurements were performed using
the EG&G Princeton Applied Research Electrochemical Impedance
System. It consists of an EG&G Model 273 potentiostat, a
Schlumberger 1255 Frequency Response Analyzer, and Model
388 software used to control the system and acquire the data.
The EIS parameters were calculated from the impedance spectrum
using the EQUIVCRT software program from EG&G. A brief
overview describing the electrochemical techniques of EIS,
linear polarization, and potentiodynamic polarization is
given in Appendix A.
Electrolyte Preparation
The electrolyte used in the three accelerated tests contained
0.05-percent sodium chloride and 0.40-percent ammonium sulfate,
two salts commonly found in industrial, atmospheric environments.
The particular concentrations of the salts have been used
in the Mebon Prohesion salt-spray test and are recommended
by the Q-Panel Company, Cleveland, Ohio. Reagent-grade sodium
chloride and ammonium sulfate were used to make up the electrolyte
for the immersion experiments and the salt solution for the
cyclic tests.
Accelerated Test Procedure Identification
and Modification
Immersion Experiment
An
experiment involving continuous immersion in an electrolyte
was chosen for accelerated testing because it provided a
severe environment that accelerates water penetration into
the coating, a significant failure mechanism that occurs
on bridge coatings.
Immersion Test
Procedures
To quantify the characteristics
of the coating and steel as the coating deteriorates in
an electrolyte-saturated environment, 14 flat, coated steel
specimens were exposed to an electrolyte containing 0.05-percent
chloride and 0.40-percent ammonium sulfate. For each coating
and surface condition, two steel panels were used. In addition
to the laboratory-prepared samples, two test specimens
were
fabricated from a weathered bridge section obtained from
IDOT. TABLE 14 lists the number
of immersion cells by coating type and surface condition.
The immersion cells consisted of a 20-cm (8-in)
long, 8-cm (3-in) diameter, translucent polyvinyl chloride
(PVC) pipe
to which an 8-cm (3-in) PVC flange was attached. The coated
test panels were placed between the flange and tightened
with four bolts, as seen in FIGURE
64. A rubber gasket between the upper flange and the
coated test panel prevented electrolyte leakage from occurring.
A PVC cap was placed on top of the cell to prevent evaporation
of the electrolyte. Periodic EIS measurements were performed
using a graphite anode and a saturated calomel reference
electrode (SCE) placed at the top of the cell.
Cyclic Test I
The cyclic
(Prohesion) salt-spray test was chosen for evaluation because
wet/dry cycling has been shown to correlate with outdoor
weathering exposure more realistically then the standard
salt-fog test, ASTM B117. The failure mechanism associated
with wet/dry cycling is similar to water/electrolyte immersion
in that osmotic pressure causes water and other ions, such
as chloride and sulfate, to diffuse and concentrate in the
coating near the steel substrate. Thus, it was thought to
be a good alternative test to the immersion experiments.
It was decided that a cyclic test with only the salt spray
would be run to determine whether the cyclic salt spray alone
is a good method for determining coating performance and
durability.
Cyclic Test I Procedure
To
quantify the characteristics of the coating and steel as
the coating deteriorates in a wet/dry cyclic environment,
41 flat and non-flat, steel panels coated with 4 of the 5
coatings were exposed to a cyclic salt fog. The four coatings
were the VOC-compliant coating and the thermally sprayed
zinc, aluminum, and zinc/aluminum. Two or three coated panels
for each coating and surface condition were tested for statistical
significance. TABLE 15 lists
the number of panels for cyclic test I by coating, surface
condition, and geometry. The salt solution used was an electrolyte
consisting of 0.05-percent sodium chloride and 0.40-percent
ammonium sulfate.
TABLE 16 gives
a summary of the cyclic experimental procedure. Before testing,
the test
panels were photographed and initial EIS measurements run
on the flat panels by placing them in an immersion cell filled
with an electrolyte of 0.40-percent ammonium sulfate and
0.05-percent sodium chloride. The samples were then placed
in the salt-fog chamber and were exposed to a modified cyclic
Prohesion salt-spray cycle for 28 d (672 h). The cycle consisted
of 1.5 h salt spray, followed by 1-h dry cycle at 35°C.
This differs slightly from the Prohesion cycle as given by
the Q-Panel Company, where the salt spray is for 1 h. It
was observed in initial tests with the Prohesion cycle that
it took approximately 15 to 20 minutes for the chamber to
fill completely with salt fog. The slightly longer spray
time allowed the test samples to encounter a more evenly
distributed salt spray for a full hour. After 14 d, the flat
samples were taken out and EIS measurements were performed.
After 28 d, a final EIS measurement was made on the flat
panels. All 41 test panels were photographed to show any
changes in the coating, and ASTM Standard 610, Evaluating
the Degree of Rusting on Painted Surfaces, was performed.
The salt-fog chamber used in the tests was
a Q-Fog Corrosion Chamber SF/MP450 manufactured by the Q-Panel
Company, Cleveland,
Ohio. The test panels were placed in the salt-fog chamber
on plastic ledges that are attached to the wall of the
chamber, as recommended by the Q-Panel Company for the cyclic
test.
In addition, flow rate and air pressure were periodically
adjusted to maintain an even distribution of salt spray
in the chamber.
Cyclic Test II
The cyclic
salt-spray, freeze/thaw, and ultraviolet-exposure test was
chosen for the same reasons as the cyclic salt-spray test;
however, it has the additional benefit of providing thermal
stressing due to the freeze/thaw cycle and elevated temperature
achieved in the ultraviolet exposure. The ultraviolet exposure
also subjects the coatings to possible chemical breakdown
of the constituents in the organic coatings. In addition,
any water that penetrated the coating in the salt-spray portion
of the cycle would freeze in the freeze/thaw cycle and expand
in volume and could cause cracking and loss of adhesion.
Also, the higher temperatures in the ultraviolet exposure
might drive off water from the coating. This continual cycle
of water penetration, expansion due to freezing, and evaporation
at elevated temperature represents an accelerated cycle of
a northern-type exposure of rain or snow, freezing conditions,
followed by drying conditions with sunlight and heating of
the bridge surface.
Cyclic Test
II Procedure
To
quantify the characteristics of the coating and steel as
the coating deteriorates, 44 flat and non-flat, steel
panels coated with the 5 coatings were exposed to a cyclic
salt-fog, freeze/thaw cycle, and carbon-arc-generated ultraviolet
radiation. The five coatings were the VOC-compliant coating,
thermally sprayed zinc, aluminum, and zinc/aluminum, and
the weathered red-lead/alkyd topcoat. Two or three coated
panels for each coating and surface condition were tested. TABLE
15 lists the number of panels for cyclic test II by coating,
surface condition, and geometry.
TABLE 16 gives
a summary of the cyclic experimental procedure. Before testing,
the test
panels were photographed and initial EIS measurements run
on the 18 flat panels. The samples were then placed in the
salt-fog chamber and were exposed to the modified, cyclic,
Prohesion salt-spray cycle for 7 d (168 h). The on/off cycle
time was the same as for cyclic test I. After 7 d, the test
panels were taken out and placed in a freezer. The initial
temperature was slightly above 0°C (32°F). The
final temperature of -23°C (-10°F) was reached
in about 2 h, and held for 24 h. After freezing, the samples
were immediately taken out of the freezer and placed in the
ultraviolet (UV) weatherometer. The UV exposure period was
8 h on, 4 h off, for 7 d. The temperature in the UV weatherometer
was initially at ambient temperature, but rose to about 60°C
(120°F) in about 1 to 2 h. After seven days in the UV-weatherometer,
the flat panels were taken out and EIS measurements performed.
The cycle was repeated for a total exposure of 30 d (720
h). Afterwards, the test panels were taken out and a final
EIS measurement was made on the flat panels. All 44 test
panels were photographed to show any changes in the coating,
and ASTM Standard 1014, Evaluating the Degree of Rusting
on Painted Surfaces, was performed.
The salt-spray experiments
were conducted in the Q-Fog Salt-Fog Chamber. The UV-weathering
cycle was done in an
Atlas Model XW-W weatherometer that uses Sunshine Carbon-Arc
Lamps to provide the ultraviolet radiation. The freezer
used for the freeze/thaw cycle was a True Manufacturing Company
Model T-23F, [0.57-m3 (20-ft3)] upright
freezer. It was purchased from Pierce Food Service Equipment
Company, Countryside, Illinois.
RESULTS AND DISCUSSION
Immersion Experiments
Immersion experiments were performed on eight, thermally
sprayed (TS) test panels, four test panels coated with a
VOC-compliant coating, and two test panels cut from a weathered
bridge section containing a lead (Pb) primer and alkyd topcoat.
The TS-coated test panels were immersed for 174 d, two each
of the VOC-compliant coatings were immersed for 92 and 98
d, respectively, and the two weathered bridge sections were
immersed for 72 d. FIGURES 65a, 65b,
and 65c show representative EIS Nyquist plots for the
TS-Zinc, Pb/Alkyd, and VOC-compliant coatings as a function
of immersion time.
Thermally Sprayed Coatings
FIGURE 66a shows a plot of
the high-frequency section of the EIS scan for a TS-zinc-coated
test panel illustrating the increase in coating resistance
as given by the increasing semicircle. The straight line
going off of the scale is actually a second semicircle at
the lower frequencies due to the steel corrosion rate. The
second semi-circle was absent on the EIS scans for the TS-Al-
and TS-Zn/Al coated test panels, indicating that steel corrosion
was not yet measurable on these coatings.
FIGURES 66a and 66b show
the consumption rate of the thermally sprayed coatings; the
corrosion rate of the steel underneath the TS-zinc coating;
and wmax, the frequency at maximum phase
angle versus immersion time. The TS coatings initially showed
a high coating consumption rate of 102 to 635 µm/yr
[(4 to 25 mil/yr (mpy)], which decreased with time to approximately
25 µm/yr (1 mpy). The sacrificial coatings are actively
corroding and protecting the steel substrate. Assuming a
constant consumption rate, the 300-µm (4-mil) thick
coatings would be completely consumed in 12 years of electrolyte
immersion. The immersion test has accelerated the coating
consumption rate threefold, given an estimated service life
of 40 years for a 300-µm thermally sprayed coating thickness.
In addition, corrosion under the thermally
sprayed coatings was measurable immediately upon immersion
in the electrolyte.
The EIS measurements indicated that electrolyte penetrated
through the TS-zinc coating to the steel substrate. Initially,
the corrosion rate of the steel substrate was 128 µm/yr
(5 mpy), but decreased to 25 µm/yr (1 mpy) after 20
d. Though it appears that the TS-zinc coating is sufficiently
protecting the steel substrate. Corrosion of the steel under
the TS-Zn/Al coatings was also not observed. The EIS scan
for the TS-Al coating, however, showed an additional diffusional
element due to ionic movement in the coating, most likely
towards the steel substrate, and suggesting that corrosion
of the steel may become measurable in a short time.
The frequency
at the maximum phase angle, wmax,
is plotted in FIGURE 66b. The wmax decreased with
time and with decreasing consumption rate for the thermally
sprayed coatings, amplifying the change from a fivefold decrease
in consumption rate to a three to four orders-of-magnitude
decrease in wmax. On the other hand, wmax due
to the steel under the TS-zinc coating stayed relatively
constant, although the corrosion rate decreased from 128
to 25 µm/yr (5 to 1 mpy). As noted earlier, the TS-zinc
is protecting the steel, which is reflected in the relatively
constant value of wmax. A significant change
in wmax would probably not occur until
the TS-zinc coating had been consumed or was not sacrificially
protecting the steel, causing the steel corrosion rate to
increase to higher values.
Pb/Alkyd and VOC-Compliant Coatings
FIGURE
65b shows EIS Nyquist plots for the Pb/alkyd-coatings
as a function of immersion time. Initially, one semicircle
was observed. After 2 d immersion, two semicircles were
measured that continually became smaller with time. The
first semicircle is representative of the Pb/alkyd coating
and the second is due to the steel substrate. Theoretically,
for a weathered coating, one would expect an EIS scan with
three semicircles representing the alkyd topcoat, the lead
primer, and the steel substrate properties. However, visual
observation of the test-panel surface under immersion showed
areas of exposed steel where significant corrosion was
occurring. This provides evidence that the second semicircle
on the EIS scan is due to steel corrosion and not the lead
primer. The Pb/alkyd coating properties appear to be lumped
together into a single semicircle on the EIS scans and
can be represented by one coating resistance.
FIGURE 65c shows
EIS Nyquist plots as a function of immersion time for the
VOC-compliant
coatings. One high-impedance semicircle was obtained, indicative
of a highly insulative coating. However, the high initial
coating resistance decreased after 29 d, indicating there
was an initial uptake of electrolyte into the coating.
Further changes in the coating resistance were small, but
they still
indicated further electrolyte penetration into the coating.
FIGURES 67a and 67b show
the coating and polarization resistance, and wmax as
a function of immersion time for the Pb/alkyd and VOC-compliant
coatings. FIGURE 67a shows
coating resistance decreasing for both coatings. This is
indicative of a coating absorbing electrolyte and becoming
less resistive. However, the VOC-compliant coating is still
five orders of magnitude higher in resistance than the
Pb/alkyd coating, meaning it is still insulative and providing
a barrier
for moisture penetration toward the steel substrate. Steel
corrosion was not observed under the VOC-compliant coatings.
On the other hand, the Pb/alkyd coating gave a relatively
low coating resistance that continued to decrease with
time, indicating that the coating has degraded. In addition,
corrosion
of the steel substrate was observed from the EIS measurements
and confirmed visually. However, the polarization resistance,
Rp, appeared to be high -- three orders of magnitude
higher than obtained from experiments done on bare-steel
rods of known area in the same electrolyte. A possible
reason is that Rp measured on the test panels
is due mostly to the exposed steel areas. However, the
total area
of the test panel, including the area covered by the Pb/alkyd
coating, was used in the calculation. This area is larger
than the actual corroding steel area and would give an
apparently larger Rp than the actual value.
More importantly, the EIS measurements are
able to distinguish between the highly resistive VOC-coating
that is beginning
to degrade and the weathered Pb/alkyd coating with corrosion
of the steel occurring underneath. Furthermore, the immersion
experiments can accelerate coating degradation in a reasonable
length of time. Extrapolation of the VOC-compliant coating
resistance to values observed with the weathered Pb/alkyd
coating give immersion times of between 350 to 500 d (1
to 1-1/2 yr). In addition, corrosion of the steel underneath
the coating would be measurable before this time. Such
a
timeframe for an accelerated test is reasonable given that
long-term field exposure takes 3 to 5 years before meaningful
data is obtained.
FIGURE 67b shows wmax as
a function of immersion time for the Pb/alkyd and VOC-compliant
coatings. The wmax for the steel under
the Pb/alkyd coating shows values indicative of a significant
corrosion rate, i.e., above 25 µm/yr (1 mpy). This confirms
that the apparent polarization resistance measured is incorrect
due to the area term. On the other hand, wmax for
the two coatings shows the same trend even though the coating
resistances are much different in value. This suggests that wmax is
a useful parameter for determining the onset and extent of
steel corrosion underneath a coating, but not necessarily
for characterizing the level of coating degradation. Fortunately,
however, coating resistance is an excellent parameter to
characterize the state of the coating. In addition, the coating
capacitance can be used to further quantify water penetration
into the coating, however, it was not calculated in this
task.
In conclusion, it appears that electrolyte
immersion combined with EIS is a good method to accelerate
coating degradation
and corrosion of the steel substrate underneath. EIS measurements
allow determination of the consumption rate of sacrificial
coatings, quantification of coating degradation, and determination
of the onset and extent of steel corrosion. The electrochemical
properties of coating resistance and capacitance, polarization
resistance, and wmax are good parameters
that can be used to correlate the performance of metallic
and organic coatings subjected to an accelerated, corrosive
environment. Although immersion times of approximately
1 year are needed to obtain significant coating degradation,
the onset of steel corrosion under the coating will occur
in a much shorter time.
Cyclic Accelerated Tests
Two
accelerated tests consisting of a cyclic (Prohesion) salt-spray
test (cyclic test I) and a cyclic (Prohesion)
salt-spray, freeze/thaw, and carbon-arc UV-exposure test
(cyclic test II) were performed on 85 flat and non-flat test
panels coated with TS-zinc, aluminum, and zinc/aluminum,
and a VOC-compliant, coating system. Flat test panels were
also cut from a weathered bridge section taken out of service
and that contained a lead primer/alkyd topcoat coating system.
The test panels were subjected to cyclic test I for a total
of 672 h, and cyclic test II for 720 h. The salt solution
used in the salt spray was an electrolyte of 0.4-percent
ammonium sulfate and 0.05-percent sodium chloride.
In general, cyclic test I subjected the test
panels to a longer salt-spray exposure (twice as long as
cyclic test
II), which caused more salt solution to penetrate into
the coatings. This was especially detrimental to the sacrificial
TS coatings, which are porous, and the weathered Pb/alkyd
coating that was already naturally degraded. However, the
combination of salt spray, freeze/thaw, and UV exposure
represented
a more severe test that not only allowed salt penetration
from on/off cycling of the salt spray, but also allowed
chemical and mechanical breakdown of the coatings due to
the freeze/thaw
and UV-exposure cycle. A longer exposure period for cyclic
test II is recommended because it would allow a higher
degree of salt penetration, coating degradation, and possible
steel
corrosion to occur after several salt spray, freeze/thaw
and UV-exposure cycles.
Non-flat Panel Results
FIGURES
68a1, 68a2, 68b1, 68b2, 68c1, 68c2, 68d1, and 68d2 show
representative before-and-after photographs of the four
coatings on the two non-flat test panels subjected to cyclic
tests I and II. TABLE 17 lists
the corrosion rating of each coating and test panel on
a scale of 1 to 10 according to the ASTM-D610 visual corrosion
rating standard, with 10 representing a coating of excellent
performance and durability, and 1 indicating a coating
of poor performance and durability.
The VOC-compliant and
TS-zinc coating performed the best of the four coatings,
showing excellent coating performance.
The TS-zinc showed excellent durability and the VOC-compliant
coating showed better-than-average durability. Both coatings
had visual ratings of between 8 and 10, performing well in
the accelerated tests with virtually no corrosion occurring
on the surface. Some yellow staining was observed on one
of the TS-zinc-coated test panels that was due to the consumption
of the zinc. However, several of the VOC-compliant coated
test panels showed several small areas of steel corrosion
on the welded bracket or the nut-and-bolt area. Though these
corroded spots were not enough to decrease the rating significantly,
they are noted because they probably occurred due to the
difficulty in uniformly coating the non-flat area. The coating
thicknesses in these areas were thinner compared to the rest
of the flat panel area. In addition, one of the VOC-compliant
coated test panels subjected to cyclic test II showed cracking
along a nut and bolt as well as on the welded bracket. The
cracking was caused by the thermal stressing from the freeze/thaw
cycle and subsequent UV exposure at elevated temperatures
and this decreased the durability rating of the coating.
These results highlight the usefulness of using non-flat
test panels to rate coating performance because such observations
were not seen on the TS-zinc or VOC-compliant coated flat
test panels. The corrosion rating for the TS-Zn/Al-coated
test panels was between 5 and 6, indicating moderate coating
performance and better-than-average durability. Although
rust from the steel was not observed, the TS- Zn/Al coating
showed visible signs of consumption, with many white "pits" where
corrosion of the coating had occurred. The surface of the
coating was generally rougher than before testing, and the
nut-and-bolt area showed fair amounts of coating consumption.
This made the coating aesthetically unpleasant. However,
overcoating the TS-Zn/Al with a topcoat or a TS-polymer may
solve this problem and would also increase coating performance
and durability.
The corrosion rating for TS-aluminum was the
worst of the four coatings, with a wide scatter of values
between 1.5
and 8.5. Coating performance and durability was moderate
to poor. The poor rating was due to significant consumption
of the aluminum that caused large amounts of aluminum corrosion
deposits on the surface of the coating, as seen in FIGURES
68a1 and 68a2. Steel corrosion was also observed on the nut-and-bolt
areas and at the weld and crevice between the two right-angle
brackets. As noted for the TS-Zn/Al, an organic or TS-polymer
overcoat might solve the problem of coating performance,
although it appears once the overcoat is compromised, significant
consumption of the TS- aluminum coating would occur, which
would further delaminate the overcoat.
In conclusion, the TS-zinc and VOC-compliant
coated non-flat test panels gave the best coating performance
and durability
of the four coatings. The TS-Zn/Al coating gave moderate
coating performance and better-than-average durability;
the TS-aluminum gave poor coating performance and durability.
The usefulness of the non-flat test panels in cyclic accelerated
testing was demonstrated and showed cracking of the coating
and significant steel corrosion at the nut-and-bolt and
welded
bracket areas, observations that could not have been made
on flat panels alone.
Flat Panel Results
Visual Rating
FIGURES
69a1, 69a2, 69b1, 69b2, 69c1, 69c2, 69d1, and 69d2 show
representative before-and-after photographs of the five
coatings on the flat test panels subjected to cyclic tests
I and II. TABLE 18 lists the
corrosion rating of each coating and test panel on a scale
of 1 to 10, according to the ASTM-D610 visual corrosion
rating standard.
The VOC-compliant and TS-zinc coatings performed
the best of the five coatings, showing excellent coating
performance
and durability. The TS-zinc coating showed some discoloration
due to zinc consumption, but steel substrate corrosion
was not observed. The VOC-compliant coatings showed no discoloration,
cracking, or rust spots on any of the test panels.
The TS-Zn/Al and TS-aluminum coated test panels
showed moderate to better-than-average performance and durability.
Alternating areas of a white corrosion product and dark
discoloration
were observed on the TS-Zn/Al coatings. Discoloration and
aluminum corrosion pits were observed on the TS-aluminum
coatings. However, steel corrosion rust spots were not
observed on the test panels.
The Pb/alkyd coated test panels
showed poor performance and durability of the coating.
Significant steel corrosion
was observed on the surface where the steel substrate appeared
to have been exposed. However, discoloration of the alkyd
topcoat was not observed.
EIS Analysis
FIGURES
70a, 70b, and 70c show the
consumption rate of the thermally sprayed coatings, the
corrosion rate of the steel underneath the TS-coatings,
and wmax, (the frequency at maximum phase
angle) for cyclic tests I and II. The TS-zinc coating gave
negligible consumption rates throughout cyclic test I,
as shown in FIGURE 70a. This
corroborates with the excellent rating given by the visual
observations and indicates that salt or water has not penetrated
to the steel substrate. On the other hand, the TS-aluminum
and TS-Zn/Al coatings gave initial coating consumption
rates of 127 to 190 µm/yr (5 to 8 mpy), which decreased
with time to approximately 25 to 114 µm/yr (1 to 4
mpy). These two sacrificial coatings are actively corroding
and protecting the steel substrate. These results are also
corroborated by the visual rating that showed significant
coating consumption. In addition, steel corrosion rates
were observed for the TS-aluminum and TS-Zn/Al after 670
h of exposure. The corrosion rate was less than 25 µm/yr
(1 mpy) for the TS-Zn/Al, but was 241 µm/yr (9.5 mpy)
for the TS- aluminum. Since steel corrosion was not observed
visually on the surface of these coatings, corrosion must
be occurring under the TS-aluminum coating. Thus, the EIS
measurements were able to characterize the early onset
of steel-substrate corrosion under the metallic coating
before corrosion was observed visually.
FIGURE 70b shows
consumption rates for the three TS coatings subjected to
cyclic test
II. In this case, the TS-zinc showed fairly high consumption
rates before, during, and after the test. The TS-Zn/Al
and TS-aluminum consumption rates were much lower than the
TS-zinc,
but still significant. All three TS coatings are active
and are protecting the steel substrate underneath. Steel
corrosion
rates were not observed for the test panels in cyclic test
II, however. As noted earlier, the salt-spray exposure
time is half of the cyclic test, or 360 h. Increasing the
total
exposure time of cyclic test II would provide a longer
salt-spray exposure that, when coupled with freeze/thaw cycling
and
UV-exposure, would accelerate the onset of corrosion under
the coatings.
FIGURE 70c shows wmax for
the three TS coatings subjected to cyclic tests I and II.
In general, the low values of wmax indicate
active, corroding metals. The values also agree with the
results from the immersion experiments that showed similar
consumption rates and values of wmax.
As noted earlier, wmax appears to be
a sensitive indicator of consumption rate of the TS coatings.
In addition,
the onset of steel corrosion was observed by EIS in approximately
670 h of accelerated exposure time. Increasing the total
exposure time to 1400 h (2 mo) would be sufficient to further
quantify steel corrosion underneath the coatings and determine
how long the TS coatings can adequately protect the steel
substrate.
The coating resistance, polarization resistance,
and wmax for
the VOC-compliant coating subjected to cyclic tests I and
II are given in FIGURES 71a and 71b.
The coating resistance was high for all the test panels,
but decreased by two to three orders of magnitude for several
of the test panels. Electrolyte penetration into the coating
was occurring, but there did not appear to be any trend
for surface condition or accelerated test method. In addition,
a test panel with a mill scale surface subjected to cyclic
test II showed measurable steel corrosion underneath the
coating, even though corrosion was not observed visually.
Thus, it is necessary to measure the onset of steel corrosion
underneath organic coatings before it is visually seen.
Still,
a longer exposure period is needed to further validate
steel corrosion and coating degradation. Extrapolation
of the coating
resistance for two of the test panels showed that a total
exposure time of between 1500 to 1900 h (2 to 2 1/2 mo)
would be needed to reduce the coating resistance to values
simlar
to a degraded coating.
EIS was able to reduce the coating resistance
to values similar to a degraded coating. Steel corrosion
underneath
the coating would be initiated as well in that time period.
FIGURE 71b shows wmax for
the VOC-compliant coatings subjected to cyclic tests I
and II. The wmax due to the coating decreased
two orders of magnitude for the test panels subjected to
cyclic test I, following the trend of decreasing coating
resistance and indicating that the electrolyte is penetrating
the coating. The wmax due to steel corrosion
on a coated panel with a millscale steel surface was low,
indicating that significant corrosion was occurring underneath
the coating. A coated test panel with a grit-blasted surface
gave a measurable wmax due to steel corrosion
after testing, which suggests that the onset of corrosion
occurred sometime between 360 and 720 h of exposure time.
CONCLUSIONS AND RECOMMENDATIONS
Based on the research performed in this task, it can be
concluded that:
- The cyclic exposure tests and immersion experiments
combined with EIS measurements provide an early indication
of coating degradation, degree of water penetration,
and the onset of steel corrosion underneath a coating
before it is visually seen in a relatively short period
of time.
EIS measurements performed on the flat test panels
in the cyclic salt-fog test, the cyclic salt-fog, freeze-thaw,
and UV-exposure test, and the immersion experiments,
allow determination of the consumption rate of sacrificial
coatings, quantification of coating degradation, and
determination of the onset and extent of steel corrosion,
after 1 mo of cyclic exposure and 3 to 6 months of immersion.
EIS was able to distinguish between the highly resistive
VOC-compliant coatings that were beginning to degrade
and the weathered Pb/alkyd coating with corrosion of
the steel substrate underneath. Estimates made from the
change in coating resistance and frequency at maximum
phase angle with exposure period indicate that cyclic
tests of 1400 to 1900 h (2 to 3 mo) and immersion experiments
of 12 to 18 mo should provide further verification of
coating degradation and steel-substrate corrosion. These
measurements can then be correlated with EIS measurements
performed on similar coatings subjected to long-term,
outdoor exposure to further validate prediction of long-term
coating degradation and failure with these methods.
- The TS-zinc and VOC-compliant coatings showed excellent
coating performance and durability on the flat test panels.
The TS-Al and TS-Zn/Al coatings gave moderate to better-than-average
results, and the naturally weathered Pb/alkyd coating
gave poor results.
The TS-zinc and VOC-compliant coatings performed well
in the three accelerated tests, with no visible corrosion
of the steel substrate. However, the coating resistance
for the VOC-compliant coating decreased with exposure
time, indicating that electrolyte was penetrating into
the coating. Corrosion of the steel was also evident
from the EIS measurements, but was not observed visually.
The TS-zinc coating showed a significant consumption
rate. Steel corrosion was not observed visually or by
EIS measurements confirming that the TS-zinc was adequately
protecting the steel substrate.
The TS-aluminum and the TS-Zn/Al coatings gave moderate
coating performance and durability. Strongly adhered
corrosion deposits on the coating surface provided evidence
of aluminum consumption for the test panels subjected
to 1 mo of cyclic salt-fog exposure. Corrosion of the
steel substrate was measurable on both coatings, even
though it was not observed visually.
The weathered bridge section with the Pb primer/alkyd
topcoat performed the worst of the five coatings. The
coating resistance was low and steel corrosion was evident
visually and from the EIS measurements. The results provide
a baseline for a weathered coating further subjected
to accelerated weathering. The changes in the EIS parameters
due to accelerated testing can be compared with EIS parameters
of coatings still in service to identify their state
of coating degradation and possibly to predict future
degradation and failure.
- The TS-zinc and VOC-compliant coatings gave better-than-average
to excellent coating performance and durability on the
non-flat panels containing welded and bolted brackets.
The TS-Zn/Al gave moderate coating performance and the
TS-Al showed poor results.
Modifying the flat test panel to include a nut and
bolt and welded bracket allowed coating performance and
durability to be simulated on non-flat areas of a bridge,
such as overlapping joints and welded supports. Rust
spots and cracking were observed on the nut-and-bolt
area and on the edges of the welded brackets, whereas
the flat sections of the panels were usually corrosion-free.
The TS-zinc and VOC-compliant coatings gave the best
performance, with visual ratings of 8 to 10 observed
on the test panels. Cracking of the coating and evidence
of steel-substrate corrosion at the nut-and-bolt area
were observed for the VOC-compliant coated test panels
subjected to the cyclic salt-fog, freeze-thaw, and UV-exposure
test. Thermal stresses appear to have been sufficient
to cause coating delamination. The TS-Zn/Al gave moderate
coating performance and better-than-average durability.
White pits of corrosion products and roughness of the
surface due to coating consumption were observed. The
TS-aluminum coating gave poor coating performance and
durability, with considerable amounts of aluminum corrosion
deposit seen and steel corrosion observed due to aluminum
consumption on the nut-and-bolt areas of the panel.
Based on the conclusions from this task, the following
recommendations for future work are given:
- Perform additional experiments using a longer cyclic
exposure and immersion period.
Based on estimates from the EIS parameters, a longer
cyclic exposure and immersion period would further verify
coating degradation and the onset of substrate corrosion.
The experiments should also include additional analysis
on the coated test panels, such as optical and surface
analysis, to provide supplementary evidence of coating
degradation. In addition, further refinement of the accelerated
tests can be accomplished by performing serial experiments.
Test panels will be taken out periodically and analyzed
to determine the shortest exposure period needed to determine
coating degradation and failure.
- Conduct accelerated experiments on additional thermally
sprayed and organic coatings.
In addition to the TS-zinc, TS-aluminum, and TS-Zn/Al,
a combination of thermally sprayed metal and polymer
should be investigated using the accelerated tests. Such
a coating system would more typically be used on a bridge,
since it combines the sacrificial properties of the metallic
coatings with the barrier characteristics of the polymer.
In addition, other VOC-compliant organic coatings should
also be studied to quantify their coating degradation
characteristics and to determine whether the onset of
steel corrosion can be predicted.
- Conduct EIS measurements on field-exposure test panels
and on coated steel bridges to evaluate the viability
of field EIS measurements and their correlation with
cyclic accelerated tests.
EIS measurements taken on coated test panels subjected
to long-term outdoor exposure as well as measurements
taken on coating systems presently applied to steel bridges
and in various states of degradation, should be performed.
Such measurements would allow the investigation of the
viability of field EIS measurements and the determination
of whether results from cyclic accelerated tests can
be correlated with field-obtained EIS parameters such
as coating resistance, polarization resistance, and wmax (the
frequency at maximum phase angle).
|